SH125CX
Inverters

SH125CX

The Sungrow SH125CX 125 kW multi-MPPT hybrid inverter is engineered for demanding West African and Sahel energy applications, delivering superior performance in high-irradiance, extreme-heat, and dusty environments common across rural electrification and off-grid solar projects in Mauritania and the ECOWAS region. With 10 independent MPPT inputs supporting up to 200% PV oversizing, it enables flexible microgrid configurations ideal for remote locations and energy-independent community installations. Built-in UPS-level on/off-grid switching, advanced arc fault protection, and smart energy management capabilities ensure robust, reliable operation for both new solar-plus-storage deployments and retrofit upgrades in challenging West African conditions.

Key Features

  • Up to 200% PV oversizing with 10 independent MPPT inputs and 20 A per string support for 182/210 mm high-power modules
  • Built-in ≤10 ms UPS-level on/off-grid switching with 125 kW backup rated output power
  • Up to 200 A charge/discharge current with support for lithium-ion batteries across a wide voltage range (129 V–880 V)
  • AFCI 3.0+ intelligent DC arc fault circuit interrupter with 600 m detection range
  • Smart trading ready for intelligent TOU, dynamic pricing, and Virtual Power Plant (VPP) participation
  • 100% three-phase unbalance output and 150% off-grid overload capability for 10 seconds
  • IP66 protection, C5 anti-corrosion rating, and self-cleaning air duct design for harsh environments
  • PID Zero anti-PID technology and intelligent string-level protection switch with PV-to-ground fault protection
Request a Quote

Technical Specifications

TypeMulti-MPPT Commercial & Industrial Hybrid Inverter
BrandSungrow
Phase3-phase (3/N/PE)
Weight≤128 kg
TopologyTransformerless
ApplicationCommercial & Industrial
Power Range125 kW
DC ConnectorMC4 (Max. 6 mm²)
CommunicationRS485, CAN, Bluetooth + APP, 4G (optional) / WLAN / Ethernet
CertificationsIEC 62109-1/-2, IEC 62477-1, IEC 62920, EN 55011, IEC 63027, VDE-AR-N 4105, VDE-AR-N 4110, NRS 097-2-1, UNE 207002, UNE 207001, NTS 2.1, CEI 0-16, CEI 0-21, EN 50549, EN 50530, IEC 61683, IEC 62116, IEC 61727, IEC 60068, IEC 61000-6-3, IEC 63027
Cooling MethodSmart forced air cooling
Grid Connection3/N/PE, 220 V/380 V, 230 V/400 V
Number of MPPTs10
AC Surge ArresterAC Type II
DC Surge ArresterDC Type I+II
Protection DegreeIP66
Relative Humidity0–100% (non-condensing)
Max. Input Voltage1100 V
Max. Output Current189.9 A
Max. Current per MPPT40 A
Nominal Input Voltage600 V
Dimensions (W x H x D)1095 mm x 795 mm x 360 mm
Max. AC Apparent Power125 kVA
Nominal Output Current180.4 A
Nominal Output Voltage220 V/380 V, 230 V/400 V
Nominal AC Active Power125 kW
Rated AC Grid Frequency50 Hz / 60 Hz
Anti-corrosion ProtectionC5
Nighttime Power ConsumptionNot specified
Operating Temperature Range-30°C to 60°C
MPPT Operating Voltage Range180 V–1000 V
Adjustable Power Factor Range0.8 leading–0.8 lagging
Max. Total Harmonic Distortion<3% (at 400 V AC voltage and rated power)
Max. Short Circuit Current per MPPT50 A
Max. Operating Altitude without Derating3000 m