JUPT-11000K/7000K/3000K-HD1
Transformer Station

JUPT-11000K/7000K/3000K-HD1

The SIMO Energy Smart Transformer Station is a highly integrated, containerized renewable energy solution engineered for West African solar deployment in 3MW, 7MW, and 11MW configurations. Pre-wired and pre-tested for rapid installation in remote Sahel locations and ECOWAS microgrids, this containerized system combines power conversion, protection, and intelligent controls to support rural electrification and off-grid energy independence across Mauritania and West Africa. The SF6-free design meets environmental standards while delivering reliable performance in high-temperature, dusty conditions typical of the region's energy access infrastructure.

Key Features

  • ✓Available in 3MW, 7MW, and 11MW configurations to suit a range of utility-scale solar projects
  • ✓SF6-free and Natural Ester Oil design options available for improved environmental and safety performance
  • ✓Class AA energy efficiency with full load efficiency index ≥99% per EN 50708
  • ✓MV upward arc releasing protection and LV arc protection up to IEC 61641 Class C
  • ✓Pre-wired and pre-tested in a 20' HC ISO container for rapid, simplified site deployment
  • ✓Smart LV room cooling with no air-across design for higher system availability
  • ✓Wide operating temperature range of -25°C to +60°C with optional 4,000 m high-altitude operation
  • ✓Supports Modbus TCP communication and is pre-configured with SmartLogger for seamless integration
Request a Quote

Technical Specifications

TypeOil-immersed, Conservator Type
Weight<28 t (JUPT-11000K-HD1) / <24 t (JUPT-7000K-HD1) / <18 t (JUPT-3000K-HD1)
CoolingMineral Oil: ONAF/ONAN (JUPT-11000K/7000K-HD1); Mineral Oil: ONAN / Natural Ester: KNAN (JUPT-3000K-HD1); Smart Cooling without Air-across for LV Room
FeaturesMV Upward Arc Releasing Protection, LV Arc Protection, MV Terminal Temperature Detection, MV Metering, Smart Closed-loop Control, SF6 Free Option, Natural Ester Oil Option
RMU TypeSF6 Gas Insulated / Natural Gas Insulated (up to 24 kV)
StandardIEC 62271-202, EN 50708, IEC 60076, IEC 62271-200, IEC 61439-1
Frequency50 Hz or 60 Hz
Dimensions6,058 x 2,896 x 2,438 mm (20' HC ISO Container)
CommunicationModbus TCP, Preconfigured with SmartLogger
LV Main SwitchesJUPT-11000K-HD1: ACB (4,000 A, 2x1 pcs) + MCCB (400 A, 2x12 pcs); JUPT-7000K-HD1: ACB (2,900 A, 2x1 pcs) + MCCB (400 A, 2x8 pcs); JUPT-3000K-HD1: ACB (2,900 A, 1x1 pcs) + MCCB (400 A, 8 pcs)
Max. MCCB inputs24 (JUPT-11000K-HD1) / 16 (JUPT-7000K-HD1) / 8 (JUPT-3000K-HD1)
Max. LV AC Inputs24 (JUPT-11000K-HD1) / 16 (JUPT-7000K-HD1) / 8 (JUPT-3000K-HD1)
Protection DegreeIP54
Relative Humidity0% ~ 95% (Non-condensing)
Power Rating (kVA)12,144 kVA @30°C / 11,040 kVA @40°C (JUPT-11000K-HD1); 8,096 kVA @30°C / 7,360 kVA @40°C (JUPT-7000K-HD1); 4,048 kVA @30°C / 3,680 kVA @40°C (JUPT-3000K-HD1)
Transformer Tappings±2 x 2.5%
Input Voltage Level (V)1000 V
Max. Operating Altitude1000 m / 4,000 m (Option)
Transformer Vector GroupDy11-y11 (JUPT-11000K/7000K-HD1) / Dy11 (JUPT-3000K-HD1)
Anti-corrosion ProtectionC5-M / C5-H (Optional)
LV Overvoltage ProtectionType I+II
Output Voltage Level (kV)10~35 kV
Operating Temperature Range-25°C ~ 60°C